XLPE Insulated U-1000 AR2V ARVFV Aluminium Power cables,NA2XY Low voltage

NA2XY U-1000 ARVFV600/1000V XLPE Insulated Aluminium Power cables

AL/XLPE/PVC cables are used for electricity supply in low voltage installation system, they are suitable for: 

· installation in indoors and outdoors 

· in cable ducts

· under ground

· in power and switching stations

· local energy distributions

· industrial plants

where there is no risk of mechanical damage.

 For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)

Share:

Details

XLPE Insulated,PVC Sheathed Cable,0.6/1kV

The 0.6/1 KV AL/XPLE/PVC cable (U-1000 AR2V ARVFV)plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted aluminum conductor(CU), cross-linked polyethylene insulation (XPLE), and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.

Construction

XLPE Insulated Aluminium Power cables,NA2XY Low voltage

Description: NA2XY, XLPE Insulated Aluminum Power Cable  

Conductors:Class 1 or Class 2 of plain aluminum, in accordance with IEC 60228.

Insulation:Cross-linked polyethylene XLPE

Insulation Colour:Natural or as required

Filler: Non-hygroscopic Material

Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath: Black

Voltage Rating (Uo/U):600/1000V   Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data(U-1000 ARVFV)

0.6/1kV-1 core aluminum conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
1X100.7 1.4 8.0 753.085571
1X160.7 1.4 9.0 1061.917191
1X250.9 1.4 10.6 1501.20 94115
1X350.9 1.4 11.6 1800.868115140
1X501.0 1.4 13.1 2400.641140165
1X701.1 1.4 15.0 3200.443180205
1X951.1 1.5 16.8 4000.320 220245
1X1201.2 1.5 18.4 5000.253260280
1X1501.4 1.6 20.5 6000.206300315
1X1851.6 1.6 22.6 7300.164350360
1X2401.7 1.7 25.2 9300.125414420
1x3001.8 1.8 27.8 11400.100 485475
1x4002.0 1.9 31.4 15000.0778 570545
1x5002.2 2.0 34.9 18000.0605670620
1X6302.4 2.2 39.1 22850.0469790705